Harmonic analysis and mitigation in distribution grids with high penetration of power inverters
Version
Published
Date Issued
2019-06-03
Author(s)
Type
Conference Paper
Language
English
Abstract
Inverters of large heat pumps in an urban low voltage grid generate current harmonics and cause consequently significant variations of the respective voltage harmonics. The voltage level at each grid point is not only influenced by the operation of such inverters, but higher harmonic voltage amplitudes can be expected, caused by the sum of all loads in the grid. The paper provides a comprehensive harmonic analysis of a typical urban distribution grid including heat pumps and presents insights on the variations and impact on the voltage profile of the 15th harmonic currents. An active harmonic filter was installed to enhance the power quality, by compensating the harmonic currents and by improving the voltage profile at grid points close-by the heat pumps.
Subjects
TK Electrical engineering. Electronics Nuclear engineering
ISBN
978-2-9602415-0-1
Publisher DOI
ISSN
2032-9644
Conference
CIRED 2019 Conference
Publisher
AIM
Submitter
Schori, Stefan
Citation apa
Schori, S., Höckel, M., Dalessandro, L., Rupp, A., Greuter, J., & Heiniger, L. (2019). Harmonic analysis and mitigation in distribution grids with high penetration of power inverters. CIRED 2019 Conference. AIM. https://doi.org/10.24451/arbor.19352
Note
Die Erlaubnis, diese PDF-Datei im ARBOR-Repository zu veröffentlichen, wurde eingeholt
File(s)![Thumbnail Image]()
Loading...
open access
Name
CIRED 2019 - 1022.pdf
License
Publisher
Version
published
Size
870.47 KB
Format
Adobe PDF
Checksum (MD5)
be6a1ac02aaf78c92e56a9fad875b255